DD740 Standby Power Supply |
|
| |
Wall mounting standby PSU |
|
| |
 |
|
| |
Utilising proven Thyristor technology, combined with its internal battery and alarm and metering options the DD740 is a rugged and reliable source of secure DC power. |
|
| |
|
|
|
| |
- Internal SLA battery
- 30A Tripping Current
- Battery Temperature Compensation
- Manual battery Check
- DC Current Metering
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Output Voltage:
Output Current Limit:
Input Voltage:
Input Frequency:
Input Current:
Voltage Regulation:
Output ripple:
Efficiency:
Battery:
|
24V / 30V (Nominal)
27.3V / 34.2V (Float @ 20°C)
5A
230VAC ±10%
50Hz ±5Hz
<1.5A
±2%
<2%
>80% at 35% to Full Load
19Ah |
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Dimensions:
Construction:
Weight:
Level of Protection:
|
600 x 425 x 370 mm (H x W x D)
Sheet steel wall mount enclusure
61kg with battery
IP42
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Cooling:
Temperature:
Relative humidity:
Altitude:
Safety:
EMC:
|
Natural Convection
-10 to +45°C operational
-25 to +60°C transport/storage
0 to 90% RH non-condensing
to 3000 metres
EN60950
Compliant
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Fuses:
DC Fault:
Battery:
|
Input - 4A BS88 A1
Output - 32A BS88 A1
Battery - 32A BS88 A1
Output short circuit protection
Current Limited
Temperature compensation
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Mains Present:
Charging:
DC Output Current:
|
Front panel LED indicator
Front panel LED indicator
72mm Analogue Meter
|
|
| |
|
|
|
| |
|
|
| |
 |
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
|
|
|
| |
|
|