RT10 |
|
| |
Stand alone or battery charger switch mode supply |
|
| |
 |
|
| |
|
|
| |
|
|
|
| |
- Stand alone supply or battery charger
- Universal input voltage: 85 - 264VAC
- Power Factor Correction
- MicroController monitor
- Overvoltage and Overcurrent protection
- Fan Cooled
- Hot pluggable
- Current Sharing
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Main DC Output:
DC Output Power:
Input Voltage:
Input Frequency:
Input Current:
Power factor:
THD:
Line regulation:
Load regulation:
Output ripple:
|
32V, 48V
32V/1500W, 48V/1900W
85 to 275VAC (Derated 100% to 50% power from 150VAC to 90VAC)
45-66 Hz
12A RMS max at 185VAC
9.5A at 230VAC
>0.98 at 50% to 100% load
Current <5% (full load) if voltage THD <2%
<±0.05%
terminal voltage drop by 0.42V% from zero to 34A (for passive sharing) for stand alone
better than ±0.05% for miniCSU controlled units
32V <10mV rms Psophometrically weighted, <10mV RMS (10kHz - 100mHz), <100mV p-p (10kHz - 100Mhz)
48V <10mV rms Psophometrically weighted, <10mV RMS (10kHz - 100mHz), <100mV p-p (10kHz - 100Mhz)
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Dimensions:
Mounting:
Weight:
Acoustic Noise:
|
255 x 220 x 42.2 mm (LxWxH)
1/2 19inch rack or Duvine power shelf magazine
< 2.5kg
<55dB
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Cooling:
Temperature:
Relative humidity:
Altitude:
Safety:
EMC:
|
Fan Cooled
-40 to +70°C operational
-40 to +50 Full Power range
0 to 100% RH non-condensing
to 4000 metres
EN60950
ETSI EN 300 386 V1.2.1
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Input:
Output:
Short circuit:
Over temperature:
|
Internal HRC fuse (option for both lines)
MOV surge protection
Internal fuse
Overvoltage shutdown
Can sustain short circuit at output terminals indefinately
Output power limiting
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Mains Present:
Module Fault:
Front panel Alarm:
Alarm reporting and history:
|
Green LED indicator
Red LED indicator
Orange LED indicator
Full range from MicroController system
|
|
| |
|
|
|
| |
|
|
| |
 |
|
| |
Battery temperature sensing
Battery availability test
Battery capacity test
Bespoke firmware
Conformal coating
|
Maximises battery life with temperature compensation
Continuous monitoring of battery condition.
Automatic discharge test to determine available battery capacity
Alarm levels can be programmed to customer chosen settings
Custom alarm delays to prevent nuisance alarms
Additional alarm conditions (ie battery temperature outside range)
Range of conformal coating options available
|
|
| |
|
|
|
| |
 |
|
| |
|
|
|
| |
|
|