DD760 Modular Charger System |
|
| |
Modular switched mode rectifier system |
|
| |
 |
|
| |
The DD760 system is a convection cooled modular power system. The system can provide N+1 redundancy with its hot-swappable chargers and can be configured with integrated distribution panels and a battery monitoring unit providing automatic battery discharge testing. |
|
| |
|
|
|
| |
- Convection Cooled
- Active current share
- Power Factor Corrected Input
- Hot-Swap module replacement
- Automatic Battery Discharge Testing
- Battery Temperature Compensation
- Up to 4 modules per system
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Main DC Output:
DC Output Power:
Input Voltage:
Input Frequency:
Input Current:
Power factor:
THD:
Line regulation:
Load regulation:
Output ripple:
Efficiency:
|
24V, 48V, 60V or 110V DC
350W per module @24V, 440W per module @ 48V, 60V and 110V
230VAC (185 to 264VAC )
47-63 Hz
3.5 Amp maximum, sinusoidal per rectifier module
>0.99
<5%
<±0.1%
<±0.5%
<2mV Psophometric
>90% at full load
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Dimensions:
Mounting:
Weight:
Level of Protection:
|
3U x 19" x 265mm (HxWxD)
19" rack
< 6.0kg
IP20
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Cooling:
Temperature:
Relative humidity:
Altitude:
Safety:
EMC:
|
Natural Convection
-15 to +60°C operational
-25 to +60°C transport/storage
0 to 90% RH non-condensing
to 1500 metres
EN60950
EN50081-1 & EN50082-2
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Input:
Battery:
DC fault
Over temperature:
|
Internal fuse in rectifier modules
MOV surge protection
Over discharge by low voltage disconnect
Output overvoltage shutdown
Output short circuit protection
Rectifier outputs individually fused on backplane
Shutdown with auto-reset
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Output Volts:
Load Current:
Battery Current:
Mains Present:
Rectifier Fail:
High Output Volts:
Low Output Volts:
Batteries Charged:
Battery Test Fail:
Temperature High:
|
LCD meter in DD761 monitor unit
LCD meter in DD761 monitor unit
LCD meter in DD761 monitor unit
Green LED indicator in rectifiers and volt free contact on backplane
Red LED indicator in rectifiers and volt free contact on backplane
Red LED indicator in monitor and volt free contact on backplane
Red LED indicator in monitor and volt free contact on backplane
Green LED indicator
Red LED indicator
Volt free contact on backplane
|
|
| |
|
|
|
| |
|
|
| |
 |
|
| |
Battery temperature sensing
Options:
|
Maximises battery life with temperature compensation
Up to 4 x 440W modules per 3U system
25 way internal DC distribution or 16 way 1U external DC distribution
Dual mains input
|
|
| |
|
|
|
| |
 |
|
| |
|
|
|
| |
|
|