DD763 Charger Module |
|
| |
Modular switched mode rectifier |
|
| |
 |
|
| |
The DD763 power supply module, normally forming part of the DD760 power system, is available to integrate into your system providing DC power filtered to telecoms standards. |
|
| |
|
|
|
| |
- Convection Cooled
- Active current share
- Power Factor Corrected Input
- Hot-Swap module replacement
- Automatic Battery Discharge Testing
- Battery Temperature Compensation
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Main DC Output:
DC Output Power:
Input Voltage:
Input Frequency:
Input Current:
Power factor:
THD:
Line regulation:
Load regulation:
Output ripple:
Efficiency:
|
24V 12A , 48V 10A(440W), 60V 8A (440W) or 110V 4A(440W) DC
350W per module @24V, 440W per module @ 48V, 60V and 110V
230VAC (185 to 264VAC )
47-63 Hz
3.5 Amp maximum, sinusoidal per rectifier module
>0.99
<5%
<±0.1%
<±0.5%
<2mV Psophometric
>90% at full load
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Dimensions:
Mounting:
Weight:
Level of Protection:
Connector:
|
3U x 14E x 265mm (HxWxD)
19" rack
< 1.0kg
IP20
DIN41612 - H15
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Cooling:
Temperature:
Relative humidity:
Altitude:
Safety:
EMC:
|
Natural Convection
-15 to +60°C operational
-25 to +60°C transport/storage
0 to 90% RH non-condensing
to 1500 metres
EN60950
EN50081-1 & EN50082-2
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Input:
DC fault
Over temperature:
|
Internal 4A fuse
MOV surge protection
Output overvoltage shutdown
Output short circuit protection
Shutdown with auto-reset
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Mains Present:
Rectifier Fail:
|
Green LED indicator
Red LED indicator and volt free contact
|
|
| |
|
|
|
| |
|
|
| |
 |
|
| |
Battery temperature sensing
Options:
|
Maximises battery life with temperature compensation
Up to 4 x 440W modules per 3U system
25 way internal DC distribution or 16 way 1U external DC distribution
Dual mains input
|
|
| |
|
|
|
| |
 |
|
| |
|
|
|
| |
|
|