100 Watt Power Supply / Charger |
|
| |
Stand-alone switched mode rectifier |
|
| |
 |
|
| |
The 100D is a stand alone power supply with micro-controller based advanced battery monitoring, featuring float voltage temperature compensation to maximise battery life, over discharge protection to protect the battery and automatic battery discharge testing. |
|
| |
|
|
|
| |
- Universal input voltage: 85 - 264VAC
- MicroProcessor Controlled
- Active battery monitoring and test
- Optional floating auxiliary output
- Power Factor Correction
- Wide range of DC outputs available
- Panel/Chassis or optional Din rail mount
|
|
| |
|
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Main DC Output:
DC Output Power:
Auxiliary Output:
Input Voltage:
Input Frequency:
Input Current:
Power factor:
THD:
Line regulation:
Load regulation:
Output ripple:
|
12V, 24V, 48V, 60V or 110V DC *1
100W
3.3V, 5V, 12V or 15V DC *2
85 to 264VAC
47-63 Hz
1.5 Amp maximum, sinusoidal
>0.99
<5%
<±0.1%
<±0.5%
<50mVp-p
<20mVrms (wideband)
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Dimensions:
Mounting:
Weight:
Level of Protection:
|
173 x 97 x 71 mm (LxWxH)
Panel / Chassis or DIN rail
< 0.65kg
IP20
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Cooling:
Temperature:
Relative humidity:
Altitude:
Safety:
EMC:
Protection
Input:
Battery:
DC fault
Over temperature: |
Natural Convection
-15 to +60°C operational
-25 to +60°C transport/storage
0 to 90% RH non-condensing
to 1500 metres
EN60950
EN50081-1 & EN50082-2
Internal fuse
MOV surge protection
No connection on incorrect voltage or polarity
Deep discharge via load disconnect
Internal fuse
Output overvoltage shutdown
Output short circuit protection
Output power limiting
|
|
| |
|
|
|
| |
|
|
|
| |
 |
|
| |
Mains Present:
Module Fault:
Battery Fault:
|
Green LED indicator
Red LED indicator and volt free contact
Red LED indicator and volt free contact |
|
| |
|
|
|
| |
|
|
| |
 |
|
| |
Battery temperature sensing
Battery availability test
Battery capacity test
Bespoke firmware
Conformal coating
|
Maximises battery life with temperature compensation
Continuous monitoring of battery condition.
Automatic discharge test to determine available battery capacity
Alarm levels can be programmed to customer chosen settings
Custom alarm delays to prevent nuisance alarms
Additional alarm conditions (ie battery temperature outside range)
Range of conformal coating options available
|
|
| |
|
|
|
| |
 |
|
| |
|
|
|
| |
*1 Other voltages can be supplied on a bespoke design basis
*2 This output is isolated so may be connected to give a -ve or +ve supply relative to the main output.
|
|